AlphaCell™ 195 GXL-FT

Gel Front Terminal Batteries
Nominal Specifications
  • Service life: Extended
  • Sealed VRLA: Valve regulated lead acid
  • Heat resistant: Extreme
  • Hydrogen emission: Low
  • Terminals: 16mm insert M6 thread
  • Typical runtime: 195 mins
  • Cells per unit: 6
  • Voltage per unit: 12.8
  • Conductance value: 1200
  • Max. discharge current: 400A
  • Short circuit current: 3000A
  • 10 Second volts @ 100A: 10.8
  • Impedance @ 60Hz (Ohms): 0.0041
  • Capacity at 20hrs (to 1.75VPC): 110Ah
Mechanical
  • Dimensions w/ terminals*: mm: 285H x 110W x 395D
  • inches: 11.22 x 4.33W x 15.55D
  • Weight: 34.52kg (76.29lb)
Environmental
  • Discharge: -40 to 71°C (-40 to 160°F)
  • Charge (with temp compensation): -20 to 50°C (-4 to 122°F)
  • Float charging voltage (Vdc) Float 2.27 to 2.30VPC @ 25°C cycling 2.35VPC @ 25°C
  • AC ripple charger 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P
  • Front terminals with protective covers
  • Valve regulated lead acid batteries
  • Long life gel batteries can be used outdoors
  • Ideal for telecom and cable applications